]J[ reaw dellihermal storage capacity [hc fo yticapac taehJ]-5,000-15,000-25,000A large thermal storage tank (7,500 m3) was installed as part of the chilled water air conditioning system, designed to store cold and heat overnight for daytime use. This system significantly reduces the building’s power consumption during the day. On a typical summer day, cooling demand reaches 190,000 MJ, with the thermal storage system covering the majority—153,000 MJ—accumulated overnight (22:00–07:00) at an actual transfer efficiency of 78%.42200,000150,000100,000-10,000-20,000222378012345690tMMt0heat storage inthe heat storage tank50,000heat storageheat radiationLarge-scale heat storage tank using the Underground Structure of CUBEDaily Cumulative Cooling Demand 194,836MJAmount of Heat Storage152,932MJHeat Storage Contribution10111213141516171819202178%200,000150,000100,00050,000themal storage capacity본 건물의 냉수 열원 시스템은 대형 축열조 (7,500m3)를 설치해 야간에 냉열을 저장하고 저장된 열을 낮에 이용하는 시스템을 도입했습니다. 일반적인 여름철 하루 냉방 수요는 190,000MJ에 달합니다. 그러나 열 저장 시스템이 153,000MJ을 충당하며, 이 에너지는 실제 전송 효율 78%로 야간 저장 시간(22:00–07:00)에 축적되고 있다는 사실을 준공 후 성능 검증을 통해 확인할 수 있었습니다. 이 시스템을 통해 건물의 한낮 전력 수요를 대폭 절감했습니다.
元のページ ../index.html#46